Skip to content

Transmission Lines and Impedance Matching

The primary line parameters are

SymbolMeaningSI unit
RRseries resistance per unit lengthΩ/m\Omega/\mathrm{m}
LLseries inductance per unit lengthH/m\mathrm{H/m}
GGshunt conductance per unit lengthS/m\mathrm{S/m}
CCshunt capacitance per unit lengthF/m\mathrm{F/m}

For instantaneous line voltage v(z,t)v(z,t) and current i(z,t)i(z,t),

∂v(z,t)∂z=−R i(z,t)−L∂i(z,t)∂t,∂i(z,t)∂z=−G v(z,t)−C∂v(z,t)∂t.\begin{aligned} \frac{\partial v(z,t)}{\partial z} & =-R\,i(z,t)-L\frac{\partial i(z,t)}{\partial t}, \\ \frac{\partial i(z,t)}{\partial z} & =-G\,v(z,t)-C\frac{\partial v(z,t)}{\partial t}. \end{aligned}

For sinusoidal steady state, ∂/∂t→jω\partial/\partial t\rightarrow j\omega, where j2=−1j^2=-1 and ω=2πf\omega=2\pi f. The voltage and current phasors V(z)V(z) and I(z)I(z) therefore satisfy

dVdz=−(R+jωL)I,dIdz=−(G+jωC)V.\frac{dV}{dz}=-(R+j\omega L)I, \qquad \frac{dI}{dz}=-(G+j\omega C)V.

Distributed model of a uniform transmission line.

Distributed model of a uniform transmission line.

Propagation Constant and Characteristic Impedance

Section titled “Propagation Constant and Characteristic Impedance”

It is

γ=α+jβ=(R+jωL)(G+jωC).\gamma=\alpha+j\beta= \sqrt{(R+j\omega L)(G+j\omega C)}.

It is

Z0=R+jωLG+jωC.Z_0=\sqrt{\frac{R+j\omega L}{G+j\omega C}}.

For a lossless line,

Z0=LC,β=ωLC,v=1LC.Z_0=\sqrt{\frac{L}{C}}, \qquad \beta=\omega\sqrt{LC}, \qquad v=\frac{1}{\sqrt{LC}}.

Thus,

V(z)=V0+e−γz+V0−eγz,V(z)=V_0^+e^{-\gamma z}+V_0^-e^{\gamma z}, I(z)=V0+Z0e−γz−V0−Z0eγz.I(z)=\frac{V_0^+}{Z_0}e^{-\gamma z}-\frac{V_0^-}{Z_0}e^{\gamma z}.

At the load,

ΓL=ZL−Z0ZL+Z0.\Gamma_L=\frac{Z_L-Z_0}{Z_L+Z_0}.

Reference directions for a line terminated in a load.

Reference directions for a line terminated in a load.

Special cases:

LoadReflection coefficient
Matched load, ZL=Z0Z_L=Z_0ΓL=0\Gamma_L=0
Open circuitΓL=+1\Gamma_L=+1
Short circuitΓL=−1\Gamma_L=-1

A load mismatch produces the reflected wave. Its interference with the incident wave creates fixed voltage maxima and minima along the line. Maxima are called antinodes; a minimum that reaches zero is called a node.

For load reflection coefficient ΓL\Gamma_L,

VSWR=Vmax⁡Vmin⁡=1+∣ΓL∣1−∣ΓL∣.\mathrm{VSWR} =\frac{V_{\max}}{V_{\min}} =\frac{1+|\Gamma_L|}{1-|\Gamma_L|}.

A matched load has ∣ΓL∣=0|\Gamma_L|=0 and VSWR=1\mathrm{VSWR}=1. As the mismatch increases, VSWR increases; complete reflection gives ∣ΓL∣=1|\Gamma_L|=1 and VSWR→∞\mathrm{VSWR}\to\infty.

RL=10log⁡10(PiPr)=−20log⁡10∣ΓL∣ dB.\mathrm{RL} =10\log_{10}\left(\frac{P_i}{P_r}\right) =-20\log_{10}|\Gamma_L|\ \mathrm{dB}.

An ideal match has ∣ΓL∣=0|\Gamma_L|=0 and RL→∞\mathrm{RL}\to\infty. Complete reflection has ∣ΓL∣=1|\Gamma_L|=1 and RL=0 dB\mathrm{RL}=0\ \mathrm{dB}.

Voltage standing-wave envelope on a mismatched line.

Voltage standing-wave envelope on a mismatched line.

QuantityMeaningIdeal matchComplete reflection
Standing-wave envelopeVoltage variationFlatMaximum
∣ΓL∣\lvert\Gamma_L\rvertVoltage reflection magnitude0011
VSWRVmax⁡/Vmin⁡V_{\max}/V_{\min}11∞\infty
Return loss (dB)Logarithmic power ratio∞\infty00

For a lossless line of length ll, the terminal voltage and current are related to the load quantities by

Vin=VLcos⁡βl+jZ0ILsin⁡βl,V_{\text{in}}=V_L\cos\beta l+jZ_0I_L\sin\beta l, Iin=jVLZ0sin⁡βl+ILcos⁡βl.I_{\text{in}}=j\frac{V_L}{Z_0}\sin\beta l+I_L\cos\beta l.

Substituting VL=ZLILV_L=Z_LI_L, taking Zin=Vin/IinZ_{\text{in}}=V_{\text{in}}/I_{\text{in}}, and dividing numerator and denominator by cos⁡βl\cos\beta l gives the input-impedance transformation below.

For a lossless line of length ll terminated by ZLZ_L,

Zin=Z0ZL+jZ0tan⁡βlZ0+jZLtan⁡βl.Z_{\text{in}}=Z_0 \frac{Z_L+jZ_0\tan\beta l}{Z_0+jZ_L\tan\beta l}.

Important special lengths:

LengthInput impedance
l=λ/2l=\lambda/2Zin=ZLZ_{\text{in}}=Z_L
l=λ/4l=\lambda/4Zin=Z02ZLZ_{\text{in}}=\dfrac{Z_0^2}{Z_L}
  • Insert a section of characteristic impedance ZtZ_t between the main line and a real load RLR_L.

  • At the design frequency f0f_0, make its electrical length 90∘90^\circ, or l=λt/4l=\lambda_t/4, where λt\lambda_t is the wavelength in the transformer.

  • The match is exact at f0f_0 but is generally narrowband. A complex load must first be transformed to a real resistance for this simple formula to apply.

For a quarter-wave transformer matching a real load RLR_L to a line Z0Z_0,

Zt=Z0RL,l=λt4.Z_t=\sqrt{Z_0R_L}, \qquad l=\frac{\lambda_t}{4}.

This condition follows directly from the input impedance of the transformer section:

Zin=ZtRL+jZttan⁡βtlZt+jRLtan⁡βtl.Z_{\text{in}}=Z_t \frac{R_L+jZ_t\tan\beta_tl} {Z_t+jR_L\tan\beta_tl}.

At l=λt/4l=\lambda_t/4, βtl=π/2\beta_tl=\pi/2, so the tangent terms dominate and

Zin=Zt2RL.Z_{\text{in}}=\frac{Z_t^2}{R_L}.

Requiring the main line to see Zin=Z0Z_{\text{in}}=Z_0 gives Zt=Z0RLZ_t=\sqrt{Z_0R_L}. The quarter-wave section is therefore an impedance inverter at its design frequency.

Quarter-wave transformer matching section.

Quarter-wave transformer matching section.

  • Ideal inductors and capacitors store energy without dissipating average power, so the network can provide a lossless conjugate match.

  • The series and shunt arrangement depends on which side has the higher resistance; the shunt element is placed on the high-resistance side in the topology shown below.

  • A series inductor with a shunt capacitor gives a low-pass match. Interchanging them gives the dual high-pass form.

  • L-networks are simple and useful when lumped components remain practical, but their match is frequency-sensitive.

Low-pass L-match topology.

Low-pass L-match topology.

  • For the shunt-stub arrangement shown, choose a distance dd from the load at which the normalized admittance is y(d)=1+jby(d)=1+jb.

  • Choose the stub length lsl_s so that it supplies susceptance −jb-jb; the total normalized admittance then becomes 11, producing a match.

  • Open and shorted stubs are both possible. Stub matching is convenient at radio and microwave frequencies, where distributed lines replace lumped reactances.

  • The possible solutions repeat every λ/2\lambda/2 and are generally narrowband.

Single shunt-stub matching schematic.

Single shunt-stub matching schematic.

  • Only the two stub lengths need adjustment, so the method is useful when a single stub cannot be placed at its calculated distance from the load.

  • The first stub moves the admittance to a value that the second stub can transform to the chart centre.

  • Certain loads cannot be matched for some fixed stub spacings; these form a forbidden region. Double-stub matches are also frequency-sensitive.

  • Normalize the load as zL=ZL/Z0z_L=Z_L/Z_0; for a shunt-stub design, convert it to admittance yL=1/zLy_L=1/z_L.

  • Move clockwise toward the generator on the constant-∣Γ∣|\Gamma| circle until the g=1g=1 conductance circle is reached. The outer scale gives the distance dd from the load.

  • Move along the g=1g=1 circle by adding the stub susceptance until the chart centre, y=1+j0y=1+j0, is reached. The corresponding scale reading gives lsl_s.

Smith chart path for shunt-stub matching.

Smith chart path for shunt-stub matching.

FeatureQuarter-wave transformerSingle stubDouble stub
Elementsone λ/4\lambda/4 line sectionone open or short stubtwo fixed-position stubs
Direct loadreal in its basic formreal or complexreal or complex, with forbidden regions
Adjustmentsection impedance and lengthstub length and positiontwo stub lengths
Installationneeds a different line impedanceneeds access at a calculated pointuseful when connection points are fixed
Bandwidthnarrowbandnarrowbandnarrowband

All three methods make the impedance seen by the main line equal to Z0Z_0 at the design frequency. The choice is governed mainly by load type, available line impedances, accessible connection points and tuning needs.

A 50 Ω50\ \Omega line is terminated by a real 100 Ω100\ \Omega load. The load reflection coefficient is

ΓL=100−50100+50=13=0.333.\Gamma_L=\frac{100-50}{100+50}=\frac{1}{3}=0.333.

Therefore

VSWR=1+1/31−1/3=2,RL=−20log⁡10(1/3)=9.54 dB.\mathrm{VSWR}=\frac{1+1/3}{1-1/3}=2, \qquad \mathrm{RL}=-20\log_{10}(1/3)=9.54\ \mathrm{dB}.

The reflected power fraction is ∣ΓL∣2=1/9\lvert\Gamma_L\rvert^2=1/9, or about 11.1%11.1\%. To match the same load with a quarter-wave section,

Zt=(50)(100)=70.7 Ω.Z_t=\sqrt{(50)(100)}=70.7\ \Omega.

At the design frequency, this section presents Zin=Zt2/RL=50 ΩZ_{\text{in}}=Z_t^2/R_L=50\ \Omega to the main line, eliminating the reflection there.